    Eight notices of diesel generator fuel tank failure

    2017-10-16 | Pageviews: CHANGZHOU FOAN M AND E CORPORATION
    Article Tags:

    The diesel generator has the corresponding standard fuel tank and fuel supply system. There are many kinds of fuel tank design. The generator manufacturer Ding Xin electrical machinery can be designed as a discrete tank with various capacity according to the requirements. Users can also design their own fuel tank, the use of diesel generator fuel tank, the user should pay attention to the following matters needing attention:

    Eight notices of diesel generator fuel tank failure.

    A tank, after placement, the highest oil surface can not be higher than a diesel generator base 2.5 meters, if the oil depot oil surface should be higher than 2.5 meters, between large oil and diesel generator plus a daily fuel tank, let the oil pressure can not be directly sent to more than 2.5 meters. Even during the shutdown of the diesel generator, it is not possible to allow the fuel to enter the diesel generator through the oil inlet line or the fuel injection line.

    Two, the fuel supply and return oil tank area should be equipped with a hole separator, to reduce the heat exchange of diesel generator.
    Three, the capacity of the fuel tank must be guaranteed daily supply.

    Four, some customers make their own tank, these tanks should pay attention to the spare diesel generator tank, with stainless steel or steel plate to make. Can't paint or plating in the inside of the tank, because they can easily react with diesel, may cause some damage caused by impurities in the diesel generator, diesel quality, cleanliness and efficiency of combustion.

    Five, the resistance at the mouth of the oil can not exceed all diesel generator performance data set on the use of clean filter specified value. This resistance is based on half the fuel tank.

    Six, fuel oil return pipeline connection, should not cause diesel generator tubing fuel shock wave.

    Seven, the fuel supply pipe end position should be higher than the diesel generator tank bottom of about 50MM, to prevent sediment and water are sucked into the oil supply pipe;

    Eight, the storage area of the tank must be safe to prevent fire, tanks or oil drums must be placed in visible places, appropriate away from the diesel generator point, and strict regulations prohibit smoking.